전기용융흔의 단락 판단 구별기준방안 제시에 관한 연구
정은수, 정성구 · 한국화재감식학회 학회지 · 2020
Determining the short circuit of molten rock found at the site when determining the cause of the fire is a very important clue to estimate an electrical fire or ignition point. Characteristics such as pores, metal structures, and boundary surfaces, which are the determining factors of short circuit wounds, are quantified with objective numerical data. As a result, the difference by the thickness of the boundary surface is analyzed as the most suitable criterion for determining whether the melt is shorted or not, and the cause of the difference is due to the difference in the occurrence time of the shorting wound due to the coating melt.