Газообразование при появлении дефектов силовых масляных трансформаторов

И.Н. Автаев, П.Н Автаев, Н.М. Александров et al. · Энергетик · 2019

The most common and reliable method for detecting a defect in an oil transformer is the chromatographic analysis of gases in oil. In this case, exceeding the concentration of individual gases in most cases does not allow localize and determine the cause of electrical (electric arc and partial discharges in oil) and thermal defects (thermal decomposition of oil, aging of solid insulation) occurrence. The method of detecting and localizing a defect by measuring short-circuit resistances from the sides of the highest and lowest voltages, on the other hand, allows to detect defects that affect gas formation arised in the course of manufacturing and operation. The difference in short-circuit resistances measured from the sides of the higher and lower voltages, reduced to one side of the transformer, is directly dependent on the magnitude of the circulating currents created by the stray fields expressed as a percentage, that is, the percentage of uncompensated turns (circulating current) of the windings with current . Uncompensated winding turns with a current of more than 2.0% and uneven load of the LV1 & LV2 windings of transformers with split windings of more than 20% lead to discharges in the contact joints of short-circuited loops and plates of the magnetic system.