스마트 외피 시스템의 최적제어에 의한 에너지 절약 효과의 해석 연구
남윤광, 홍성기, 조성환 · 대한설비공학회 동계학술발표회 논문집 · 2018
In this study, we have analyzed and studied energy savings when office buildings with smart skin simulated by TRNSYS. Typically Smart Skin means a complex skin system that adjusts the conditions of the building's exterior in response to the external environment to maintain the optimal indoor environment. During winter season, SHGC and dimming control enable maximum heating load to be saved by 4%, and lighting loads can save up to 30%. And during summer season, the cooling load can be reduced by 19.2%, and the lighting load can save 55%. When it collected monthly data by optimum control, it able to find a savings of 17.65% in winter and 8.13% in summer.