평판형 증발부를 갖는 루프히트파이프의 역구배 성능에 대한 실험적 연구

임경택, 배장현, 조영탁 et al. · 대한기계학회 춘추학술대회 · 2019

The performance at the adverse tilt of a loop heat pipe(LHP) with a flat square evaporator was experimentally investigated. The LHP was made of stainless steel and methanol was used as working fluid. The maximum heat load was 300 W(heat flux of 19 W/㎠) and its heating area was 40 ㎜ × 40 ㎜. The coolant inlet temperature at the condenser was maintained at 10℃. The LHP operated successfully at the adverse tilt angle of 90˚ for the heat load range of 38 W to 240 W. A cold start-up was demonstrated for a step heat input of 183 W. Sintered nickel was used as a capillary structure in the evaporator. The lowest thermal resistance was 0.186℃/W.