The three dimensional numerical analysis is performed on the turbulent flow in the room space of simple geometry with contaminant generation. The contaminant is lighter than air density, so buoyancy effect is caused by the density difference between air and contaminant. Flow pattern and concentration distribution due to the density difference is investigated. SIMPLER algorithm is used to solve the Navier-Stokes equation governing steady, incompressible turbulent flow and standrd turbulent model is used to consider the turbulece effects. From the results of this study, following conclusions were summarized. (1) As inlet velocity is decreased buoyancy effect due to density difference is increased, so aif flow pattern and concentration distribution in room are attected significantly by density difference between air and contaminants. (2) At vertical plane including outlet, air flow pattern is more affected by density difference than that of other plane. (3) Contaminated area is more wider when the density of generating contaminant is equal to air density, so ventilation plan is established respect to contaminant. (4) Contaminant concentration ishigher at left side of inlet position,but deviation of vertical concentration value is small. (5) As inlet velocity is increased the flow of remained contanimant contaminates low concentration area, so relative concentration of room is increased.`