기존 패키지 에어컨 적용 시 공동주택 바닥복사냉방의 제습 가능성 분석

정병진, 박정인, 문순영 et al. · 대한건축학회지회연합회 학술발표대회논문집 · 2011

Recently, there is an active research to apply the cold water to radiant floor system as the existing radiant floor heating system. However, it is experiencing difficulty with its utility because of impossible maintenance for the interior thermal environment for the dehumidification and cooling. This research therefore simulated three cases - packaged air conditioner that has been in use previously and radiant floor cooling, only packaged air conditioner, only radiant floor cooling - and set them under interior rainy season and confirmed the possibility of dehumidification for each case. We produced same condition of dry temperature of 25degrees and relative humidity of 85% as 99.2m2 apartment building and completely opened door of each room under cooling condition. The FDS of USA NIST is used as simulation program. The result of possibility for dehumidification was positive for packaged air conditioner that has been in use previously and radiant floor cooling as well as the packaged air conditioner but negative for only radiant floor cooling.

Cited by 0 works.