축냉 시스템을 이용한 냉매 과냉각 효과
이동원, 주문창, 최병진 et al. · 대한설비공학회 하계학술발표회 논문집 · 2007
This study was experimentally performed to find the methodology which can be utilized cold heat storage system for the refrigerant sub-cooling in the cooling system. The show-case system, which has annually continuing cooling load, was chosen as the reference system for this study. Comparing the result at general operation condition with that at the new condition using ice storage system, this study showed the effects of the refrigerant sub-cooling. At the condition using ice storage system, the ice making process was operated during midnight being not needed the cooling of the show-case through the continuous running of the condenser unit. And then, the refrigerant was sub-cooled using stored cold heat after being discharged from the air cooling condenser during the daytime. The cooling performance was increased owing to the sub-cooling of refrigerant during daytime, hence the running time of the compressor was effectively decreased. In other words, this study showed that power consumption during daytime can be transferred to the midnight for making use of the refrigerant sub-cooling.