Экспериментальная оценка эффективности применения вспучивающихся огнезащитных покрытий для электрических проводов и кабелей при одновременном воздействии пожара и токовой нагрузки
С. В. Пузач, Olga S. LEBEDCHENKO, Владимир Иванович Зыков et al. · Pozharovzryvobezopasnost/Fire and Explosion Safety · 2023
Introduction. In order to preserve the operability of wires and cables in fire conditions, intumescent flame retardant coatings are used, the effectiveness of their application in the case of real fire mode has not been investigated. Ai ms and purposes. The purpose of the article is to evaluate experimentally the effectiveness of the use of intumescent flame retardant coatings for electrical wires and cables under simultaneous exposure to fire and current load. In order to achieve this purpose, experimental tests on wires and cables of different brands, treated with intumescent water dispersion fire-protective paint “Ogneza-VD-K”. At the same time, the influence of heated ambient temperature on electrical parameters of wires and cables, such as resistivity, inductance and capacitance, was assessed. Met hods. Experimental study of heating in a muffle furnace of wire and cable samples treated with intumescent water-dispersion fire-retardant paint. Analysis of the obtained results. Results and t heir discussion. The dependences of resistivity, inductance and capacitance of common electrical cables on ambient air temperature are obtained. It was found that for all considered cables, the short circuit occurred at ambient temperatures in the range of 180–230 °C increasing the fireproofing coating to dimensions that protect the cable from external thermal impact. In this case, the phases and amplitudes of the input electrical signal can change significantly before a short circuit occurs. It has been found that the swelling of fire retardant paint under fire conditions in a muffle furnace occurs at 400 °C and not at 200 °C as in the case of standard tests. It is shown that the dynamics of temperature change inside the muffle furnace approached the temperature regime of a real fire in the room of the MCPU (Main circulation pump units) section of the Leningrad NPP (containment) of the reactor building and in the cable room of the 3rd safety channel of the safety building. Con clusions. Working capacity of electric wires and cables treated with flame retardant should be determined in real fire conditions in the premises where these wires and cables are used.
Cited by 0 works. doi:10.22227/0869-7493.2023.32.05.49-59 Open-access PDF
Authors
References
- Fire performance of wire and cable reaction-to-fire tests :
- Advances in Fire Hazard Testing of Electrical Equipment
- Compartment temperature estimation of a multiple-layer cable tray fire with different cable arrangements in a closed compartment
- Assessment of operation of safety channel signal cables at nuclear power plants under fire conditions
- SUBSTANTIATING PASSIVE FIRE PROTECTION TECHNOLOGY FOR THE MAIN BUILDINGS OF NUCLEAR POWER PLANTS WITH WATER-COOLED REACTORS BASED ON CALCULATING FIRE RESISTANCE OF ENCLOSING STRUCTURES
- Evaluation of the Toxicity of Flame Retardant Signal Cables in Case of Fire in the Industrial Premises
- The application efficiency of intumescent coatings for power cables of safety systems of nuclear power plants under fire conditions
- Operability evaluation of electrical wires and cables subjected to simultaneous fire and current loadings