ОЦЕНКА ЭФФЕКТИВНОСТИ ВАРИАНТОВ ОГНЕЗАЩИТЫ КОНСТРУКЦИЙ ИЗ ПОЛИМЕРНЫХ КОМПОЗИТОВ НА СТЕНДЕ ЛУЧИСТОГО НАГРЕВА
А Н Гаращенко, А.В. Виноградов, Л.А. Соболь et al. · Pozharnaia bezopasnost` · 2025
Представлены результаты испытаний на стенде лучистого нагрева, проводимые с целью предварительной и оперативной оценки эффективности трех вариантов огнезащиты применительно к несущим конструкциям из полимерных композитов. Все варианты предусматривали использование вспучивающегося покрытия СГК-2. Продемонстрирована целесообразность проведения подобных испытаний, позволяющих получать важную информацию, способствующую решению задачи по обеспечению рациональной огнезащиты и заданной огнестойкости конструкций. There are presented the results of tests of fire protection samples of structures made of polymer composite (fiberglass) using an intumescent coating SGK-2 based on chlorosulfated polyethylene. There was compared the effectiveness of the coating applied on a 300х200 mm plate and two variants of combined fire protection, where as an intermediate layer the SGK-T composition with phenolic microsphere filler was used instead of heat-expanding graphite in SGK-2 or a layer of basalt fibre material MBOR-F. The temperature of the fiberglass plate was recorded, as well as the temperature between the layers of fireproofing and on the surface of the bulging layer. Standard and other modes of exposure were reproduced under heating by a packet of halogen incandescent lamps. Regulation was carried out using surface thermocouples. It has been confirmed that only when using the SGK-2 coating, it is practically impossible to ensure the fire resistance limit of load-bearing structures made of polymer composites even during 15 minutes. The option of combined fireproofing with an intermediate SGK-T layer provides the fire resistance limit of structures for 15 minutes or more, but when using a layer of MBOR-F, a significantly higher fire resistance limit is achievable. During additional tests of SGK-2 on steel plates, the possibility of reproducing various exposure modes on the stand was demonstrated. Change in the thickness of the intumescent layer was recorded; information was obtained on the temperature of the onset and bloating rate, as well as other characteristics affecting the effectiveness of fire protection. The temperature level of the beginning of bloating of the SGK-2 coating turned out to be about 195 °C, which is higher than previously indicated. It was noted that, when applying softer than standard exposure modes, their effect on the plate heating level was reduced by the reduction of the bloating rate. Such studies undoubtedly contribute to the adoption of reasonable technical solutions for fire protection and ensuring the required fire resistance limits for structures made of polymer composites and other materials.
Cited by 0 works. doi:10.37657/vniipo.pb.2025.28.90.001