積分方程式による部分放電現象のモデル化と解析
弘明 植原, 達希 岡本 · Institutional Repositories DataBase (IRDB)
A partial discharge is a discharge that occurs partially in an insulating material when a voltage is applied between electrodes.The characteristics of partial discharge change in a complex manner due to many factors such as the type of insulating material and the shape of defects in power apparatus.Therefore, the establishment of physical model that theoretically explains the partial discharge characteristics is expected, but it has not been established at this time.In this study, we focused on two partial discharge fluctuations (discharge start voltage fluctuation and discharge delay time fluctuation) that are directly related various partial discharge characteristics and also related to the physical properties of insulating materials.In addition, we modeled partial discharge and investigated the relationship with various partial discharge characteristics.Furthermore, by using these two fluctuations as parameters, an integral equation representing partial discharge characteristics was derived.On the other hand, we measured the partial discharge characteristics using a needle-plane (NP) electrode that simulates a defective part in an actual power apparatus, and compared it with the solution of the integral equation.
Cited by 0 works. Open-access PDF