高速実験炉「常陽」特殊試験報告書; 補助冷却系による崩壊熱測定試験
Motoo Doi, 松村 寿晴, 坂口 俊英 et al. · Institutional Repositories DataBase (IRDB) · 1981
Decay heat measurement by auxiliary cooling system was conducted to measure the decay heat after 75 MWt 1st cycle operation of the Joyo experimental fast reactor. Auxiliary primary pump was started after plant condition reached warm stand-by, then main primary and secondary pumps were stopped after parallel operation with auxiliary loop and primary loops. Test results: (1)Decay heat was approximately 470 kW. It contains the heat which lost from the auxiliary piping in the reactor vessel. (2)Auxiliary cooling system had enough capacity to remove the decay heat at this test condition. (3)After main primary pumps were stopped, temperature difference between hot leg and cold leg of the main primary loops soon reached the limitation of this test. So this test was stopped and plant condition was reverted to warm stand-by.