АНАЛІЗ ВПЛИВУ ТИПУ ЗАХИСТУ МАСЕЛ НА ВМІСТ РОЗЧИНЕНИХ ГАЗІВ У СПРАВНИХ ТРАНСФОРМАТОРАХ

О.В. Шутенко, В.В. Довгалюк · The Scientific Issues of Ternopil Volodymyr Hnatiuk National Pedagogical University Series pedagogy · 2026

Abstract. The results of an analysis of the concentration of gases dissolved in oil are presented for 426 serviceable 110-330 kV transformers of the non-hermetic construction. The analysis revealed that, for transformers of non-hermetic execution, the presence of free access to atmospheric oxygen leads not only to accelerated oxidation of the oil compared to transformers with nitrogen and film protection, but also to significant differences, both quantitative and qualitative, in the composition of gases dissolved in the oil. In particular, the analysis revealed an extremely low hydrogen content (in oil samples taken from transformers of non-hermetic construction, a maximum hydrogen content was detected in only 3.23 % of all samples). This characteristic is due to the diffusion of hydrogen into the atmosphere, owing to its low solubility coefficient in oil. Another characteristic feature of the gas content in the oil of serviceable transformers of non- hermetic construction is the abnormally high ethylene content (in oil samples taken from the tanks of transformers of non- hermetic construction, a maximum ethylene content was detected in 47.96 % of all samples). However, such a high ethylene content is not caused by the degradation of hydrocarbons present in transformer oils, but is the result of secondary oxidative reactions that occur intensively in the presence of free oxygen from the air. The characteristics of the qualitative composition of the oil samples described above are also reflected in the quantitative analysis of gas concentration levels. In particular, the number of oil samples in which the concentration of a particular gas is below the chromatograph’s detection limit is determined not only by the amount of energy required to break the chemical bonds between specific hydrocarbon compounds, but also by the solubility coefficients of that gas in the oil. The analysis showed that the proportion of samples from serviceable transformers in which gases concentrations exceeded the limit values corresponding to Level III (i.e. the presence of a defect) did not exceed 10 %. However, the percentage of samples exceeding Level III varied significantly for each gas. The paper also presents the results of an analysis of the distribution laws governing the ratios and gases growth rates in serviceable transformers of non-hermetic construction. The results presented in the article indicate that the type of transformer oil protection has a significant influence on the content of gases dissolved in the oil and, consequently, that this influence must be taken into account when adjusting the limit values for gases concentrations and growth rates.

Cited by 0 works.

Authors