Симетрування навантажень вузлів електричних мереж з використанням двофазних симетрувальних установок

M. Y. Burbelo, M. V. Kuzmenko, О.О. Бірюков et al. · Visnyk of Vinnytsia Politechnical Institute · 2010

In the case of the possibility of incomplete balancing of loadings it is expedient to use two-phase balancing installation, as they provide the minimal economic charges at admissible value of asymmetry factor of the voltage in a reverse sequence. The conditions of balancing of loadings are obtained, presented as active conductivity of reverse sequence in systems of coordinates relatively phases A, B and C, that provides an opportunity of essential reduction of errors due to the identity of construction of measuring channels of two phase balancing installations.