АНАЛИЗ ВЫСШЕЙ ГАРМОНИЧЕСКОЙ СОСТАВЛЯЮЩЕЙ И МОДЕЛИРОВАНИЕ ТРАНСФОРМАТОРА С КРИВОЙ НАМАГНИЧИВАНИЯ В СЕТЯХ С ИЗОЛИРОВАННОЙ НЕЙТРАЛЬЮ ПРИ ОДНОФАЗНОМ КОРОТКОМ ЗАМЫКАНИИ
Александр Николаевич Кустов, Violetta Iosifovna Zatsepina, Витольд Бялы · Vesti vysshikh uchebnykh zavedenii Chernozem ya · 2023
The article presents the process of modeling the mode of operation of the distribution electric network 6(10)-35 kV with isolated neutral at single-phase short circuits to the ground. Particular attention is paid to the possibility of analyzing the highest harmonic components of the zero sequence in power lines in supertransition and steady-state single-phase short circuit mode. For this purpose, a model of power transformers with higher voltages of 6, 10 and 35 kV was compiled, taking into account the saturation characteristics of the steel core. Modeling of the electric network was carried out in the Matlab software complex. The influence of network configuration, line length in overhead lines was studied.