ЭКСПЕРИМЕНТАЛЬНЫЕ ИССЛЕДОВАНИЯ ЭФФЕКТИВНОСТИ СИСТЕМЫ АКТИВНОГО ЭКРАНИРОВАНИЯ МАГНИТНОГО ПОЛЯ ВБЛИЗИ ГЕНЕРАТОРНЫХ ТОКОПРОВОДОВ ЭЛЕКТРОСТАНЦИЙ

I.V. Bovdui, Волошко Александр Валерьевич, Виниченко Елена Владимировна et al. · Tekhnichna Elektrodynamika · 2014

Experimental research of efficiency of feed-forward, feed-back and complex systems for power frequency magnetic fields active shielding system in work place near power stations generator bus with orthogonal system of magnetic executive coils. Experimentally confirmed the possibility of magnetic field level reducing in given zone of 3÷5 times. The possibility of magnetic field level reducing in limited area of the space in 15÷20 times. References 5, figures 4.

Cited by 0 works. Open-access PDF