Ограничение провалов напряжения в системах электроснабжения промышленных предприятий
Корнилов Геннадий Петрович, Алексей Юрьевич Коваленко, Николаев Александр Аркадьевич et al. · Electrotechnical Systems and Complexes · 2014
The object of the study is the power supply system of the industrial enterprise, which includes the main step-down substation, distribution networks and 10 kV bus. The analysis of voltage dips on one section of the tire was carried out when a fault occurred. On the basis of mathematical modeling the study obtained the resulting voltage produced change when the sectional reactor was connected. The mathematical model of the substation was developed in MATLAB using Simulink package, which facilitated the study of the effect of the reactor application on the value of the resulting voltage in the 10 kV bus. The research group defined and developed the relationships between the reactor resistance and system parameters such as short-circuit power and resistance of supply lines. A method for calculating the parameters of the reactor in the presence of motor load in 10 kV buses was offered. The possible ways limiting the engine shut down during voltage drops were considered. The proposed technical solutions will reduce the number of shutdowns of power consumers during voltage drops in the power supply lines.
Cited by 0 works.